產品標準 Standard of product
本產品按GB/T12527-2008標準生產,同時還可根據用戶需要按國際電工委員會推薦的IEC標準、英國標準、德國標準和美國標準生產。
The product is manufactured according to the standard of GB/T12527-2008. At the same time ,it can also be manufactured according to IEC,BS,DIN and AEIC upon request.
電纜導體允許的長期最高工作溫度
Max permissable continuous operating temperature of conductor
聚氯乙烯架空電纜:70℃
PVC insulated aerial cable: 70℃
聚乙烯絕緣架空電纜:75℃
PE insulated aerial cable: 75℃
交聯聚乙烯絕緣架空電纜:90℃
XLPE insulated aerial cable:90℃
短路時(最長持續時間不超過5S)電纜導體的最高溫度應不超過:
Max temperature of the conductor during short-circuit (5s maximum duration) shall not exceed :
聚氯乙烯絕緣架空電纜:160℃
PVC insulated aerial cable: 160℃
聚乙烯絕緣架空電纜:130℃
PE insulated aerial cable: 130℃
交聯聚乙烯架空電纜:250℃
XLPE insulated aerial cable: 250℃
電纜敷設時環境溫度應不低于:-20℃
The ambient temperature under installation should not be lower than -20℃
電纜的允許彎曲半徑
電纜外徑(D)小于25㎜,應不小于電纜外徑的4倍
電纜外徑(D)等于或大于25㎜,應不小于電纜外徑的6倍
The bending radius of cable are recommended as follow:
When the diameter of cable is less than 25㎜:not less than 4 times of the cable’s OD
When the diameter of cable is more than and including 25mm: not less than 6 times of the cable’s OD
當電纜使用交流系統時,電纜的額定電壓至少應等于該系統的額定電壓;當電纜適地直流系統時,該系統的額定電壓應不大于電纜額定電壓的1.5倍
When the cable are used in the alternative current systerm,rated voltage of cables should be at least equal to the rated voltage of the system;when the cables are used in direct current system, rated voltage should not exceed than 1.5 times of the rated voltage of the cables
不同環境溫度下載流量修正系數
Correction factor of current rating under different ambient temperature
材料
Material
電壓
Rated voltage
kv
導體溫度
Conductor temperature
℃
實際環境溫度℃Actual temperature
10
15
20
25
30
35
40
45
50
55
載流量修正系數
Corection factor of current rating for ambient termperature